Above 290 kilowatts of heating or cooling, a hotel needs a GACS

A building automation and control system reads out a building’s installations and adjusts them. Since 1 January 2026 it has been mandatory in large non-residential buildings, and from 2030 in medium-sized ones too.

· Editors Hotel Magazine

A tidy plant room with insulated pipes and grey control cabinets with green indicator lights.
Editorial image

In the plant room of a large hotel stand installations that heat, cool and ventilate rooms, lobby, kitchen and other spaces. Add up their capacity and you know whether the hotel has needed a GACS since 1 January 2026. For that sum, the nominal capacity of all technical building systems that provide heating or cooling in spaces where people stay counts. Koninklijke Horeca Nederland (KHN), the hospitality trade body, writes that mainly larger hospitality businesses, hotels and conference venues with extensive climate installations may be affected by the obligation.

GACS stands for gebouwautomatiserings- en controlesysteem, a building automation and control system. The Netherlands Enterprise Agency (RVO) describes it as an advanced system that reads out and controls the climate and energy installations in a building. KHN describes how it works: the system continuously monitors and analyses the installations and adjusts them where needed, from heating, cooling and ventilation to lighting and energy management. It may be a complete product from one supplier or assembled from parts of different brands. Which manufacturer the system comes from does not matter.

A thermostat and a ventilation grille on a white wall in a quiet corridor.
Editorial image

The threshold is 290 kilowatts. From 1 January 2026, non-residential buildings with a heating or cooling installation of more than 290 kW must have a GACS, and from 1 January 2030 the threshold is lowered to 70 kW. A non-residential building is any building without a residential function, including a factory hall or workshop, as long as the building is heated or cooled for people. Buildings that also contain homes do not have to comply with the obligation. When adding up, only spaces where people stay count. Spaces where people do not work, or only occasionally, do not count, nor do spaces with an indoor temperature below 15 degrees Celsius or that are only kept frost-free. For heat pumps the nominal capacity as defined in the standard EN 14511-4:2013 applies.

What must the system be able to do? Check, record and analyse consumption permanently and be able to adjust it. Test the energy efficiency of the building and detect efficiency losses in the installations, and inform the manager about possible improvements. It must let connected installations and devices communicate and work with other systems that change energy use, such as storage systems, solar panels and charging points. That last point makes the system the link between a hotel’s installations and the charging points in the car park.

Whether an existing system suffices is measured with the standard NEN-EN-ISO 52120-1. The score runs from class A, a very efficient control, via B, an improved standard control, and C, standard, to D, an inefficient control. Existing buildings must reach at least class C. For the technical management and analysis functions in chapter 7 of the standard, class B is mandatory. Anyone building a new non-residential building must, from 29 May 2026, reach at least class B for the GACS and class A for chapter 7. A building that now scores a D must therefore move to at least a C.

A person with sufficient technical knowledge or an external specialist can test the system with the checklist the government has drawn up, based on the same standard. The results go into a report. The inspector of the competent authority will probably discuss that report during an inspection. If the system does not yet fully comply, an improvement plan follows. An existing building automation system, which controls the climate installation automatically, can do only a limited amount: it probably does not comply. An energy management system mainly has a reporting function and meets the requirements only at an advanced level.

Who is accountable? The owner, not the tenant. An owner of a let building must comply with the obligation themselves, even if the building is used by an operator, and the competent authority can look at the lease to see who bears the obligations. That competent authority is the municipality, which can outsource the task to an environmental agency. For a hotel in a rented building it therefore pays to know who owns the climate installation.

Since 29 May 2026 the requirements have been extended and spelled out more clearly. For large and medium-sized buildings, obligations are added for monitoring and controlling the indoor environmental quality, such as temperature and ventilation, and for automatic control of the lighting. The aim remains the same: less energy use. The benefits RVO names are less wasted energy and therefore lower energy costs, more comfort in the building and installations that work more efficiently. All possibilities for improvement must be carried out, unless an exception laid down in the Omgevingsregeling (the ministerial regulation under the Environment and Planning Act) applies. RVO writes that a GACS also contributes to solutions for grid congestion.

In brief

Mandatory since 1 January 2026: buildings without a residential function with more than 290 kW of heating or cooling

From 1 January 2030: threshold 70 kW

Existing buildings: at least class C (NEN-EN-ISO 52120-1), new buildings from 29 May 2026 at least class B

Accountable: the owner of the building; competent authority is the municipality