Does a hotel have to install charging points?
Since 29 May 2026 the Dutch Buildings Decree has contained new requirements for charging points at non-residential buildings. The more parking spaces, the more has to be in place.

Since 29 May 2026, new requirements for charging points have applied to buildings without a residential function, called utility buildings in the rules. A hotel with a car park is such a building. The requirements come from the revised European directive on the energy performance of buildings (EPBD IV). The Netherlands has translated it into national rules in the Besluit bouwwerken leefomgeving (Bbl, the Buildings Decree), and the first obligations came into force on 29 May 2026.
Three terms come up again and again. A charging point is a connection with which one vehicle can charge at a time. Pre-cabling is everything needed to be able to install charging points later, such as cables and cable routes. Instead of cables, pull cords may be used temporarily, for example because grid congestion does not yet allow a connection. Conduit provisions are the lightest form of preparation: just an empty pipe, so that cables can later be installed without breaking up the ground or walls.

For a new non-residential building with more than five car parking spaces, at least half of the spaces must be pre-cabled and there must be at least one charging point per five spaces. The rest get conduit provisions. The requirement applies to parking spaces used by residents, visitors and employees. With 30 parking spaces that comes down to six charging points and pre-cabling for at least 15 spaces. New offices get a stricter requirement: at least one charging point per two spaces. That is a different type of building from a hotel.
A major renovation can also trigger the requirement. This concerns a major renovation, in which more than 25 percent of the surface of the building envelope is renovated, and the obligation applies only if the renovation also affects the car park or parking area, or the electrical infrastructure of the building or the parking area. There is a way out: the obligation lapses if the cost of the charging infrastructure is higher than 10 percent of the total renovation costs. The owner must substantiate this with quotes, and the competent authority decides case by case whether the exception applies.
For existing hotels without renovation plans there is a later date. For existing non-residential buildings with more than twenty parking spaces, from 1 January 2027 there must be one charging point per ten parking spaces. Anyone who would rather prepare than install can, as an alternative, make half of the parking spaces ready. What counts for a building project is the moment of the permit application: if it was submitted before 29 May 2026, the old requirements apply. These assumed at least one charging point for the whole parking area with more than ten bays, plus empty conduits for one in five bays. The completion date plays no role.
Which spaces count? All parking spaces that belong to the building, inside and outside, as long as building and parking area have the same owner and the area is meant for the users of that building. Spaces on municipal land in public space fall outside. For the number it makes no difference which type of charging point is chosen: an AC charging point counts as much as a DC fast charger, and a hotel is free to choose what best fits the expected charging demand.
The building does not have to operate the charging points itself. An external party may install and operate them, because the obligation concerns the presence of charging infrastructure, not who operates it. The owner does remain the point of contact for the competent authority and must make sure the charging points meet the requirements of the Bbl. If the grid is full, there are routes to charge anyway within the existing connection, for example dynamic load balancing, which prevents overload, or solar panels. With smart charging the system adjusts the charging process automatically, for example to the load on the grid, the electricity price or the supply of renewable power.
The rules of the previous directive are still on the information pages of the Dutch Information Point for the Living Environment (IPLO). For a new non-residential building with more than ten parking bays they say: at least one charging point and a conduit provision for at least one in five bays. With 15 bays that is one charging point and three conduit provisions, one of which is already at the charging point. For an existing building with more than twenty parking bays, at least one charging point has applied since 2025. If several building functions, such as a residential, an office and a retail function, use the same parking spaces, the heaviest rules apply. Every charging point must meet NEN 1010, even if it is not mandatory. Electric bicycles are not among the electric vehicles in these rules, because the Road Traffic Act 1994 excludes pedal-assisted bicycles from the definition of motor vehicles. For charging an e-bike the ordinary Bbl rules for electrical installations do apply.
In brief
Non-residential buildings, new or majorly renovated, more than 5 parking spaces: 1 charging point per 5 spaces (permit application from 29 May 2026)
Pre-cabling for at least half of the spaces, conduit provisions for the rest
Existing buildings with more than 20 spaces: 1 charging point per 10 spaces from 1 January 2027
Obligation lapses in a renovation if the cost exceeds 10 percent of the renovation costs